Permit Number: T21CM08197
Parcel: 12712119A

Address:
20 N LEONORA AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08197
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/17/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not resolved. Mechanical ventilation is required for dwelling units per Section R403.6, IECC 2018; natural ventilation is not an option. The mechanical ventilation can consist of supply, exhaust, or a combination of the two. Reference: Sections 401.2 and 403.1, IMC 2018 and Section R403.6, IECC 2018. [Initial comment: Mechanical ventilation is required for dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018 and Section 403.3.2, IMC 2018.]
03/17/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved