| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/17/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. Mechanical ventilation is required for dwelling units per Section R403.6, IECC 2018; natural ventilation is not an option. The mechanical ventilation can consist of supply, exhaust, or a combination of the two. Reference: Sections 401.2 and 403.1, IMC 2018 and Section R403.6, IECC 2018. [Initial comment: Mechanical ventilation is required for dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018 and Section 403.3.2, IMC 2018.] |
| 03/17/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/06/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |