Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a project valuation (labor + materials).
10/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The City of Tucson has not adopted the 2018 Uniform Building Code. The 2018 International Building Codes with Local Amendments are the relevant codes for this project. For the relevant codes, see https://www.tucsonaz.gov/pdsd/building-codes Note that the Residential Provisions of the 2018 International Energy Conservation Code are applicable to apartment dwelling units. Reference: Section R101.5, IECC 2018.
3. Provide the manufacturer's equipment data and specifications for the new equipment. Reference: Sections 301 and 304.1, IMC 2018.
4. Show the location of all condensing units mounted on the roof. Provide guards for equipment located within 10 feet of a roof edge. Reference: Section 304.11, IMC 2018.
5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
6. Mechanical ventilation is required for dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018 and Section 403.3.2, IMC 2018.
7. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
10/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide drawings sealed by an Arizona Registrant that show the plumbing changes resulting from the removal of the chiller system. Reference: Section 107.2.1, IBC 2018.
10/28/2021 ROBERT SHERRY WATER REVIEW Completed
10/29/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/05/2021 STEVE SHIELDS ZONING REVIEW Approved
11/05/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
11/18/2021 JVINCEN1 FIRE REVIEW Approved