Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08197
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide a project valuation (labor + materials). |
| 10/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. The City of Tucson has not adopted the 2018 Uniform Building Code. The 2018 International Building Codes with Local Amendments are the relevant codes for this project. For the relevant codes, see https://www.tucsonaz.gov/pdsd/building-codes Note that the Residential Provisions of the 2018 International Energy Conservation Code are applicable to apartment dwelling units. Reference: Section R101.5, IECC 2018. 3. Provide the manufacturer's equipment data and specifications for the new equipment. Reference: Sections 301 and 304.1, IMC 2018. 4. Show the location of all condensing units mounted on the roof. Provide guards for equipment located within 10 feet of a roof edge. Reference: Section 304.11, IMC 2018. 5. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. 6. Mechanical ventilation is required for dwelling units. Reference: Sections R403.6 and R503.1.2, IECC 2018 and Section 403.3.2, IMC 2018. 7. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
| 10/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide drawings sealed by an Arizona Registrant that show the plumbing changes resulting from the removal of the chiller system. Reference: Section 107.2.1, IBC 2018. |
| 10/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/05/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/05/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/16/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
| 11/18/2021 | JVINCEN1 | FIRE | REVIEW | Approved |