Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T21CM08160
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/25/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/28/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a grounding detail for the new 200 amp electrical service shown on plan sheet E- 502. Ref; 2018 IBC 107.2.1, 2017 NEC art 250. |
| 10/29/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/29/2021 | STEVE SHIELDS | PLANNING-CITY HALL | REVIEW | Passed | |
| 10/29/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/01/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/29/2021 | PCAMARE1 | COMMUNICATIONS | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/29/2021 | VVERA1 | OUT TO CUSTOMER | Completed |