Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM08126
720 N OLSEN AV


TRANSMITTAL DATE: January 31, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

COMMENT: Please provide all pipe lengths. The developed length (Distance from meter to the furthest appliance) appears to be the distance from the meter to the Barbecue grill, (70 ft). Based on a developed length of 70ft the 1" pipe will over provide 220,BTU this will result in an undersized pipe. It is recommended that you run a dedicated line to the line tankless water heater (resulting in a smaller demand on the line) or a dedicated line to BBQ (resulting in a smaller developed length)

COMMENT: Residential will review the application on the next submittal