Permit Number: T21CM08041
Parcel: 124060970

Address:
1211 E 9TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08041
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2018 and Section 107.2.1, IBC 2018.
2. Provide sealed drawings showing the installation of the new, exterior, tankless water heater. Reference: Section 107.1, IBC 2018.
10/13/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/13/2021 ROBERT SHERRY WATER REVIEW Reqs Change Verify the presence of a reduced pressure backflow assembly for the water service to the common laundry facility. Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
10/20/2021 KROBLES1 ZONING REVIEW Passed
10/20/2021 KROBLES1 ENGINEERING REVIEW Passed
10/20/2021 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Passed
10/20/2021 KROBLES1 FIRE REVIEW Passed
10/20/2021 KROBLES1 BUILDING-COMMERCIAL REVIEW Passed