Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08041
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/13/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2018 and Section 107.2.1, IBC 2018. 2. Provide sealed drawings showing the installation of the new, exterior, tankless water heater. Reference: Section 107.1, IBC 2018. |
10/13/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/13/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the presence of a reduced pressure backflow assembly for the water service to the common laundry facility. Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
10/20/2021 | KROBLES1 | ZONING | REVIEW | Passed | |
10/20/2021 | KROBLES1 | ENGINEERING | REVIEW | Passed | |
10/20/2021 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
10/20/2021 | KROBLES1 | FIRE | REVIEW | Passed | |
10/20/2021 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Passed |