Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM08039
Parcel: 12215394A

Address:
3450 E SENECA ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM08039
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM08039
Residential Addition
October 18, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

a. A full site plan with all setbacks, elevation drawings, lot coverage calculations and other plot plan standards is required.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
10/29/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/03/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08039

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Sample drawings are shown as an example: https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and lines supporting the alterations, R106.1.1. Show the utility lines requiring upgrade or replacement.

FLOOR PLANS:

1 Provide a floor plan showing the location of all window and door openings.
2 Show the wall composition between the dwelling and carport for fire rating determination (any windows require enclosing). The exterior dwelling wall requires 1/2” sheet rock applied over a T1-11 type wall sheathing if the wall is not a masonry product, R302.6.
3 Show any door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.
4 Identify the room with a door entering into the dwelling. An opening from a garage directly into a sleeping room is not permitted, R302.5.1.

SECTIONS - DETAILS:

1 Show a cross-section detail of the proposed exterior wall, R106.1.1. Show 3/8” structural or ½” non-structural wall sheathing of the proposed exterior wall, R106.1.1.
2 Provide a Garage wall detail showing a 6” minimum separation of exterior siding or sheathing above finished grade, R317.1 item 5. Also, show a pressure treated sill plate with ½” x 10” @ 4’ O.C. anchor bolts with 7” embedment into a 12” x 12” continuous foundation with #4 bear reinforcement. Show any weep screed with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. This may require a design with concrete stems.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5.
2. Garage Receptacle Location: an outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review