Permit Number: T21CM08027
Parcel: 10408005F

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08027
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08027 & T21CM08028

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
T21CM08027 - Service Building
1. The fire extinguishers under the life safety systems data box is missing the applicable code information. Provide the applicable code information that is missing.
2. The occupant load factor used in the occupant load calculation for the service area is incorrect. This most resembles a 200 gross use load factor. Provide the correct occupant load factor and recalculate the occupant load in accordance with Table 1004.5.
3. The occupant load on the cover page doesn't match the occupant load on Sheet G1.3. Additionally the break room and training room is calculated inappropriately. Please recalculate all areas and correlate all applicable requirements.
4. Ensure a clear path is maintained through the tool area for egress.
T21CM08028
1. No drawings submitted for this permit #. Submit construction drawings for the cosmetic building.

MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/subject to field approval
ELECTRICAL REVIEW COMMENTS
Denied

E1.0 SERVICE BUILDING LIGHTING PLAN:
Need a comcheck for interior lighting renovation.
Cannot locate Notes 7 and 11.
E1.1 SERVICE BUILDING POWER PLAN: Could not locate Notes 1, 12, and 14.

PLUMBING REVIEW COMMENTS:
Denied

1), Lavatory faucets need to be automatic type per -Tucson ICC 2018 Plumbing code amendments 412.11 & 419.6 Update
P3 & P7 fixture information on plan page P4.0
2). Add urinal side wall/partition to center clearance measurements to plan page A2.2 -IPC 405.3.1
3). Ice maker/coffee boxes detail #6 on plan page P4.0 needs to include proper backflow devices. -IPC 608.17.1.2
4). Add the floor drain/trap primer information to plan page P4.0 plumbing fixture schedule. -IPC A106.3.1
5). Add a floor drain trap primer detail to plan page P4.0. -IPC A106.3.1
11/02/2021 SSHIELD1 ENGINEERING REVIEW Passed
11/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08027 & T21CM08028
4755 N Oracle Rd – C-3
TI – Auto Sales

TRANSMITTAL: November 2, 2021
This site is located in the C-3 zone (UDC 4.7.22). Auto Sales is an allowed use in the zone, UDC Table 4.8-4 subject to Use Specific Standards 4.9.9.G.1& .2.

1. It does not appear that plans were submitted for “COSMETIC” TI. Either submit the plans or withdraw the permit.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/16/2021 JPEELDA1 FIRE REVIEW Reqs Change The fire extinguishers under the life safety systems data box is missing the applicable code information. Provide the applicable code information that is missing.
The occupant load on the cover page doesn't match the occupant load on Sheet G1.3. Additionally the break room and training room is calculated inappropriately. Please recalculate all areas and correlate all applicable requirements.
Ensure a clear path is maintained through the tool area for egress.