Permit Number: T21CM08023
Parcel: 141186260

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08023
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2021 ROBERT SHERRY WATER REVIEW Reqs Change Comment not resolved. The water meter shown on the plumbing drawing is a sub-meter for the landlord's use. The initial comment is for the water meter supplied by Tucson Water and the backflow preventer protecting the municipal water distribution system. [Initial comment: Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.]