Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2021 IMONSHI1 ZONING REVIEW Approved
10/19/2021 IMONSHI1 ENGINEERING REVIEW Passed
11/02/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08007
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLUMBING PLANS:

1. Clarify if the water heater is new or existing, P2801.1.

MECHANICAL PLANS:

1. Provide a permit number for the replaced HVAC system, R303.9, M1302.1.
2. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.
2. Show one 20 AMP branch circuit for the dishwasher/disposal; this circuit may not serve other locations, E3703.8 City of Tucson Amended.
3. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3901.7. Show the circuit number.
4. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.
5. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.