Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07995
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM07995 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. The occupancy class is incorrect. This is a mixed use building with three uses S-1/M/B. The main use is a S-1 facility. While the mixed use won't require separation in accordance with Section 508 please correct the code analysis data. Additionally, the break room is an assembly space. 2. No egress plans are provided. Provide a thorough egress planning showing all exits and travel distances that meet the requirements of Chapter 10. The egress plan should show the location of all proposed furniture, aisles and proposed layouts and exit lighting and signage. 3. The break room is not calculated in the occupant load. Provide an accurate occupant load for the break room. 4. Provide a wall schedule along with associated wall tags. 5. Indicate on the RCP the required amount of emergency lighting in accordance with Section 1008. 6. Indicate if the existing structure has a fire sprinkler system and a fire alarm systems. 7. The plans indicate details that do not exist in the construction drawings. Provide all referenced details. 8. Provide mechanical plans for review. 9. Provide plumbing plans for review. 10. Provide a complete set of accessible plans that include accessible routes, accessibility details, and signage. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Provide an interior lighting compliance certificate. PLUMBING REVIEW COMMENTS: N/A |
| 10/27/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. |
| 10/28/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/28/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/28/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/15/2021 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/15/2021 | VVERA1 | OUT TO CUSTOMER | Completed |