Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07989
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2021 | GSLEIGH1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | Please identify building number for this work. |
| 10/27/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018 |
| 10/28/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM07988 & 7989 4670 N Circuit Rd. – C-3 New Detail Building & Sales Remodel TRANSMITTAL: October 28, 2021 This site is located in the C-3 zone (UDC 4.7.22), Vehicle Rental and Sales is an allowed use subject to Use Specific Standards 4.9.9.G.1& .2 (Table 4.8-4). 1. Zoning has reviewed the building plan for compliance with DP21-0274 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 10/28/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/01/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM07988 & T21CM07989 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. The occupant load factor used for the business area is incorrect. The occupant load factor for business is 150 in accordance with Table 1004.5. Please correct and correlate any applicable requirements. 2. The total occupant load for the detail center is incorrect. The correct factor is present but it was not calculated. Please correct and correlate any applicable requirements. 3. No egress plans are provided. Provided thorough egress plans that show all related egress components and a travels distances from remote points to public way. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance. Reference IECC Section 505.1 PLUMBING REVIEW COMMENTS: Approved |
| 11/04/2021 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 11/16/2021 | JPEELDA1 | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2021 | VVERA1 | OUT TO CUSTOMER | Completed |