Permit Number: T21CM07973
Parcel: Unknown

Address:
9434 E 26TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07973
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide structural calculations for the new shade structure.
2. General: Please provide a Special Inspections Certificate with Parts A and B completed.
10/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/20/2021 ROBERT SHERRY WATER REVIEW Passed
10/27/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM07973
9434 E 26th St – R-1
Tucson Water Well E-016A – SCADA Upgrades

TRANSMITTAL: October 27, 2021
This site is located in the R-1 zone (UDC 4.7.8). A Utility Distribution System is a permitted use in this zone (Table 4.8-2), subject to Use-Specific Standards 4.9.11.A.1, .2, .5, .8, .9, .11 and submittal and approval by a Zoning Examiner Special Exception Procedure, Section 3.4.3.

1. A development package (DP) meeting the requirements of Administrative Manual Section 2-06 must be submitted and approved prior to this permit. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type, “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/27/2021 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning Comments
10/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/27/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/03/2021 JPEELDA1 FIRE REVIEW Approved