Permit Number: T21CM07963
Parcel: 10321025E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07963
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TI-1.0; Development Data: Please provide an occupant load calculation on this sheet. Break down the calculation into Storage and Office.
2. Sheet TI-1.0; Development Data: If the occupant load is 15 or fewer, the IBC Section 2902.2 requires only a single restroom. Please verify and indicate on this sheet.
3. Sheet TI-1.0; Development Data: If the occupant load is 15 or fewer, the IBC Section 2902.6 requires no drinking fountain. Please verify and indicate on this sheet.
4. Sheet TI-1.1; Leasing Office Plan: The plan indicates Sections 6/A5 and 7/A5 at the interior partition walls. The sections provided indicate 4 and 5. Please coordinate the section references and sheet numbers for clarification.
5. Sheet TI-1.1; Interior Elevations: The elevation indicates Section 6/A5 at the cabinet. Please coordinate the section reference and sheet number for clarification.
6. Sheet TI-1.1; Window Elevations: The elevation indicates Section 3/A5 at the window head. Please coordinate the section reference and sheet number for clarification.
7. General: Please provide written responses to all review comments.
10/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/20/2021 ROBERT SHERRY WATER REVIEW Completed
10/27/2021 STEVE SHIELDS ZONING REVIEW Approved
10/27/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/27/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/16/2021 JPEELDA1 FIRE REVIEW Approved