Permit Number: T21CM07957
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07957
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/10/2022 ROBERT SHERRY WATER REVIEW Completed
01/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the plumbing plan and the waste & vent isometric by providing a vent for the North floor sink. [Initial comment: Provide waste and vent isometrics. Reference: Section 107.2.1, IBC 2018.].
2. Verify with the need for a grease interceptor with PCRWR, not PCHD. [Initial comment: Verify that the Pima County Regional Wastewater Reclamation Department will not require the use of a grease interceptor for this kitchen. Reference: Section 1003.3 (C), IPC 2018, as amended by the City of Tucson.]
01/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved