Permit Number: T21CM07949
Parcel: 136346040

Address:
3220 S AMES PL

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM07949
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T21CM07949
New Garage (1st Review)
3220 S AMES PL

TRANSMITTAL DATE: 10/14/2021

DUE DATE: 10/21/2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The provided site plan is missing some required information (setbacks, lot coverage calculation, adjacent zoning, north arrow, etc.) For full site/plot plan requirements see


02. COMMENT: Provide an elevation drawing showing the height of the proposed structure measured from design grade to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge) of the highest gable of a pitched or hipped roof. (You can use the image provided on the 1st page of plans as your elevation drawing and add/draw the heights)


03. COMMENT: Detached accessory structures may not exceed 12' in height.


04. COMMENT: The setback requirement is based on the height of the adjacent wall (6' or 2/3 the height of the wall), provide the wall height so required setbacks can be determined.

05. COMMENT: The total gross floor area (GFA) of the accessory structure may not exceed 25% the GFA of the principle structure.



If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
10/14/2021 SROGERS2 ENGINEERING REVIEW Passed
11/01/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide the manufacturer’s calculations, data and sealed Arizona engineered plans for the pre-designed assembly, R106.1.

Show the electrical service to the property. An overhead line requires appropriate clearance above buildings, E3604.2.1.