Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2021 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T21CM07945 – Additions

Plot Plan Review (1st Review)

2741 W Leawood Dr / R-1 Zone

TRANSMITTAL DATE: 10/13/2021



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Setback requirements for the front perimeter yard in an established area are 20’ measured from the structure to the property line. For this carport, the setback would be measured from the posts of the structure to the property line. The overhang can extend from the post into the setback for an extra 2’ but the post itself must be 20’ from the property line.



For a lot with a curved front yard the minimum street yard depth may be measured from a straight line drawn between the front lot corners, rather than measured directly from the curved front property line. For a visual representation of this refer to figure 6.4.5-A:

https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-5192



On the next submittal provide the correct setback measured from the post of the structure.



For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
10/29/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/01/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide the load rating of the HHGU hanger with a fastener notation connecting to the existing wall assembly (detail #5) or show a support post carrying the roof load to a foundation.