Permit Number: T21CM07926
Parcel: 13413057D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07926
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1; Code Analysis (Line 19): The Occupancy Group on Line 19 indicates A-2. Please revise.
2. Sheet C1; Building Codes: Please remove "Amendments to the 2018 International Residential Code" and "Amendments to the 2018 International Swimming Pool and Spa Code".
3. Sheet C1 (Code Analysis Data); Sheet A2 (Floor Plan): The Code Analysis indicates "2 exits provided". The IBC Section 1016.2(5) indicates exit egress shall not pass through storage rooms. The back exit (Door D-E) may not be considered an exit. Please revise the Code Analysis.
4. Sheet A2; Floor Plan: Per the IBC Table 1006.2.1, the maximum common path of egress travel for a sprinklered B Occupancy is 100'. Please indicate on the Floor Plan this travel distance requirement is met.
5. Sheet A2; Counter Plan: Per the ICC/ANSI Section 904.3, a sales and service counter with a forward approach shall have a 30" minimum surface length, 36" maximum height above the floor, a clear floor space per Figure 305.3, and knee clearance meeting the criteria of Section 306.3. Please indicate these requirements on the Counter Plan.
6. General: A previous C of O for this space was Retail. A new C of O will be provided for the new tenant.
7. General: Please provide written responses to all review comments.
10/19/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018.
10/19/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/19/2021 ROBERT SHERRY WATER REVIEW Completed
10/26/2021 STEVE SHIELDS ZONING REVIEW Approved
10/26/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/26/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/16/2021 JPEELDA1 FIRE REVIEW Reqs Change Sheet C1; Code Analysis (Line 19): The Occupancy Group on Line 19 indicates A-2. Please revise.
Sheet C1 (Code Analysis Data); Sheet A2 (Floor Plan): The Code Analysis indicates "2 exits provided". The IFC Section 1016.2(5) indicates exit egress shall not pass through storage rooms. The back exit (Door D-E) shall not be considered an exit. Please revise the Code Analysis.
Sheet A2; Floor Plan: Per the IFC Table 1006.2.1, the maximum common path of egress travel for a sprinklered B Occupancy is 100'. Please indicate on the Floor Plan this travel distance requirement is met.

Questions:
Jennifer Peel-Davis
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov
Fire Plans Examiner