Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07926
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/13/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C1; Code Analysis (Line 19): The Occupancy Group on Line 19 indicates A-2. Please revise. 2. Sheet C1; Building Codes: Please remove "Amendments to the 2018 International Residential Code" and "Amendments to the 2018 International Swimming Pool and Spa Code". 3. Sheet C1 (Code Analysis Data); Sheet A2 (Floor Plan): The Code Analysis indicates "2 exits provided". The IBC Section 1016.2(5) indicates exit egress shall not pass through storage rooms. The back exit (Door D-E) may not be considered an exit. Please revise the Code Analysis. 4. Sheet A2; Floor Plan: Per the IBC Table 1006.2.1, the maximum common path of egress travel for a sprinklered B Occupancy is 100'. Please indicate on the Floor Plan this travel distance requirement is met. 5. Sheet A2; Counter Plan: Per the ICC/ANSI Section 904.3, a sales and service counter with a forward approach shall have a 30" minimum surface length, 36" maximum height above the floor, a clear floor space per Figure 305.3, and knee clearance meeting the criteria of Section 306.3. Please indicate these requirements on the Counter Plan. 6. General: A previous C of O for this space was Retail. A new C of O will be provided for the new tenant. 7. General: Please provide written responses to all review comments. |
10/19/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018. |
10/19/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
10/19/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/26/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/26/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
10/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/26/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/16/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Sheet C1; Code Analysis (Line 19): The Occupancy Group on Line 19 indicates A-2. Please revise. Sheet C1 (Code Analysis Data); Sheet A2 (Floor Plan): The Code Analysis indicates "2 exits provided". The IFC Section 1016.2(5) indicates exit egress shall not pass through storage rooms. The back exit (Door D-E) shall not be considered an exit. Please revise the Code Analysis. Sheet A2; Floor Plan: Per the IFC Table 1006.2.1, the maximum common path of egress travel for a sprinklered B Occupancy is 100'. Please indicate on the Floor Plan this travel distance requirement is met. Questions: Jennifer Peel-Davis 520-837-7033 Jennifer.Peel-Davis@Tucsonaz.gov Fire Plans Examiner |