Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM07899
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Per the comment response letter from Berts Electric and Plumbing co. And conversation via cell phone conversation with Craig. The 2nd submitted plan still does not contain sufficient information to meet electrical standards. Ref; 2018 IBC section 107.2.1. 1. Some of the wording on the plan is not legible. For example, see the panel schedule and building #6 lettering. 2. Specify the scope of work in detail on the electrical plan, and provide a site plan including the entire site. Not just buildings #6 and #7. 3. Indicate the rating of the OCPD for circuit #2/building 7. 4. Indicate the electrical service rating in amps, voltage and phase. 5. Indicate the service panel type (all-in-one) or (pedestal) and mounting method if applicable. 6. Provide a permanent plaque on the existing and new electrical service identifying the location of all the services and denoting all other branch circuits associated for each building as required per NEC 230.2(E). Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |