Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07899
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 10/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by a Registered Electrical Engineer registered in the State of Arizona. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Include an electrical site plan including any exterior power and lighting modifications if applicable. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
| 10/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/02/2021 | JPEELDA1 | FIRE | REVIEW | Approved |