Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM07891
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/12/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
10/27/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide a post foundation detail showing the minimum 12" depth below the undisturbed ground surface R403.1. Show a 16" by 16" size for supporting a structure with 12' beam spans. Show two each way #4 rebar reinforcement with 3" clearance from earth, R403.1.3.5.3. Sample drawings are available as an example: https://www.tucsonaz.gov/pdsd/residential-permits |