Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments, also provide a written response.

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.

2. Include complete panel schedules including load calculations, Indicate all feeder conduit, conductor sizes and types.

3. Provide a Grounding Electrode System at the Café Trailer. NEC 250.32

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
10/28/2021 NGARCIA3 OUT TO CUSTOMER Completed