Permit Number: T21CM07879
Parcel: 110110010

Address:
2602 N SWAN RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07879
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM07879
Roof top Solar Panels (1st Review)
2602 N SWAN RD

TRANSMITTAL DATE: October 25, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Please provide the slope of the roof, to verify if modules on the roof are compliant with the Fire code. If not demonstrate compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2021 VVERA1 OUT TO CUSTOMER Completed