Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM07845
Parcel: 129041800

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07845
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/18/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide exhaust for the barber area per Table 403.3.1.1, IMC 2018.
2. Demonstrate energy code compliance for the alteration to the building envelope (e.g. window replacement) using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.
10/18/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2021 ROBERT SHERRY WATER REVIEW Completed
10/19/2021 IMONSHI1 ZONING REVIEW Approved
10/19/2021 IMONSHI1 ENGINEERING REVIEW Passed
10/19/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/27/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/09/2021 JPEELDA1 FIRE REVIEW Approved