Permit Number: T21CM07800
Parcel: 116122680

Address:
1306 W SONORA ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM07800
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM07800                   
Residential Addition  
October 05, 2021  

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.  

1. Please add the zoning classification of the property along with the zoning of all adjacent parcels.
2. Add the right of way measurements for W. Sonora st. to the site plan.
3. Label the elevation drawings to reflect cardinal directions. The elevations should be labeled by North, South, East, or West.
4. The minimum front street setback in the R-2 zone is 20'. Based on the proposed wall height, a DDO is required to reduce the front street setback, as measured from the SOUTH property line, from 20' to 14'. Please return the plans with the corrections before applying for the DDO.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
10/05/2021 NMARTEL1 ENGINEERING REVIEW Passed
10/26/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed