Permit Number: T21CM07762
Parcel: 118122550

Address:
1428 S 6TH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07762
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

Electrical plan reviewer tried to contact Mr. Electric (contractor) and Roberto Flores (Applicant) via phone numbers listed in the application to ask for clarification pertaining to the scope of work. No answer from Mr. Electric.Received return call form Roberto's wife, stated that all existing electrical service equipment was demo'ed and will start from scratch.

Provide complete electrical plans including load calculations and line diagram. Designed and sealed by a registered Engineer registered in the State of Arizona.

Ref; 2018 IBC section 107.1. 2017 NEC, City of Tucson Commercial Plan Submittal Requirements

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2021 NGARCIA3 OUT TO CUSTOMER Completed