Permit Number: T21CM07739
Parcel: 12111162C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07739
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/12/2021 ROBERT SHERRY WATER REVIEW Completed
10/14/2021 SAMUEL ROGERS ZONING REVIEW Approved
10/14/2021 SROGERS2 ENGINEERING REVIEW Passed
10/14/2021 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/25/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. The voltages for the service equipment does not correlate with the 75 KVA transformers and the new panels. Please clarify.

2. Indicate all branch circuits and update the panel schedules accordingly to reflect the field conditions. NEC 408.4.
3. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.

Ref; 2018 IBC section 107.1.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
11/02/2021 JVINCEN1 FIRE REVIEW Approved