Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM07739
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/12/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/12/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/14/2021 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 10/14/2021 | SROGERS2 | ENGINEERING | REVIEW | Passed | |
| 10/14/2021 | SROGERS2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/25/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. 1. The voltages for the service equipment does not correlate with the 75 KVA transformers and the new panels. Please clarify. 2. Indicate all branch circuits and update the panel schedules accordingly to reflect the field conditions. NEC 408.4. 3. Provide compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Ref; 2018 IBC section 107.1.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
| 11/02/2021 | JVINCEN1 | FIRE | REVIEW | Approved |