Permit Number: T21CM07686
Parcel: 10409031B

Address:
4219 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07686
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The Watts LF007 is not appropriate for this application, a Watts LF009 (ASSE 1013) is approved for this use. Specify the backflow prevention assembly and show the location of the backflow prevention assembly and shut off valve on the plans. [Initial comment: The direct-connection of water to an appliance (e.g. a misting system) shall be protected against backflow. Specify the device to be used for the appliance connection. Reference: Sections 608.1 and 608.17.6, IPC 2018.]
2. Nothing on the drawings indicates a provision for an overflow. Show and note the overflow drains on the drawing. [Initial comment: Verify the existence of secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.]
02/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved