| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The Watts LF007 is not appropriate for this application, a Watts LF009 (ASSE 1013) is approved for this use. Specify the backflow prevention assembly and show the location of the backflow prevention assembly and shut off valve on the plans. [Initial comment: The direct-connection of water to an appliance (e.g. a misting system) shall be protected against backflow. Specify the device to be used for the appliance connection. Reference: Sections 608.1 and 608.17.6, IPC 2018.] 2. Nothing on the drawings indicates a provision for an overflow. Show and note the overflow drains on the drawing. [Initial comment: Verify the existence of secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.] |
| 02/08/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |