Permit Number: T21CM07686
Parcel: 10409031B

Address:
4219 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07686
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2021 JPEELDA1 FIRE REVIEW Approved
10/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The direct-connection of water to an appliance (e.g. a misting system) shall be protected against backflow. Specify the device to be used for the appliance connection. Reference: Sections 608.1 and 608.17.6, IPC 2018.
2. Verify the existence of secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
3. Primary rainwater leaders may not discharge onto a sidewalk. Reference: Section 7-01.4.1 E, Technical Standards Manual, Tucson Arizona Unified Development Code.
10/12/2021 ROBERT SHERRY WATER REVIEW Completed
10/14/2021 STEVE SHIELDS ZONING REVIEW Approved
10/14/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/14/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and also provide a written response.

Designate branch circuits and panel for the branch wiring required for all devices, fans, lighting proposed for this project. And show the location of the breaker panel. NEC 408.4.

Provide a complete panel schedule including load calculations.

Show the locations of the luminaires and provide a luminaire schedule or a detailed description of the luminaires.

Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code (OLC) for the proposed exterior canopy lighting. See section 104 OLC.

Ref; 2018 IBC section 107.2.1, 2017 NEC. Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.