Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM07681
Parcel: 13314227C

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07681
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2021 JPEELDA1 FIRE REVIEW Approved
10/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify to discharge point of the roof drains shown on sheet P-141. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
10/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/14/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/14/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/14/2021 STEVE SHIELDS ZONING REVIEW Passed
10/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and also provide a written response.

Provide separate lighting and receptacle branch circuits for each Elevator Control Room and or each Pit area. Lighting wiring methods also must comply with NEC arts 620.23, 620.24.

Ref; 2018 IBC section 107.2.1, 2017 NEC art 620.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2021 NGARCIA3 OUT TO CUSTOMER Completed