Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07681
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 10/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify to discharge point of the roof drains shown on sheet P-141. Condensate drains may not terminate over a roof drain unless the roof drain terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. |
| 10/12/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/14/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/14/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/14/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 10/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and also provide a written response. Provide separate lighting and receptacle branch circuits for each Elevator Control Room and or each Pit area. Lighting wiring methods also must comply with NEC arts 620.23, 620.24. Ref; 2018 IBC section 107.2.1, 2017 NEC art 620. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |