04/14/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. [initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018.]
04/15/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
04/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM07551
510 S Highland Ave – R-2
Classroom Addition (3rd Review)

TRANSMITTAL: April 15, 2022

This site is located in the R-2 zone (UDC 4.7.9). Education – Elementary & Secondary is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.3.D.1-7.

Zoning acknowledges your comment response. As you are proposing an expansion to this site a
Development Package (DP) meeting the requirements of AM 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the submission type “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
04/25/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans show that the building does have fire sprinklers under fire sprinkler general notes but under the code analysis it states that the building does not have a fire sprinkler system. Plans shall also indicate occupant load

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
04/25/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved