Permit Number: T21CM07551
Parcel: 12414115B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM07551
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/04/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant for the non-structural items. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide calculations to verify that adequate ventilation will be provided for the expanded classroom space. Reference: Sections 401.2 and 401.3, IMC 2018.
3. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018.
11/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.
The electrical plans noted on the Drawing Index 'E1' and 'E2' are still not included in the re-submittal.

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
11/18/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/18/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM07551
510 S Highland Ave – R-2
Classroom Addition (2nd Review)

TRANSMITTAL: November 18, 2021

This site is located in the R-2 zone (UDC 4.7.9). Education – Elementary & Secondary is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.3.D.1-7.

Zoning acknowledges your comment response. As you are proposing an expansion to this site a
Development Package (DP) meeting the requirements of AM 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using the submission type “Site Review”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
12/06/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show the fire department access
Plans shall show if the building has fire sprinkler and or fire alarm system
Plans shall show the deferred submittals