Review Details: OTHER

Permit Number - T21CM07490
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed Essentially doubling the developed length of the natural gas piping may result in some of the branch piping becoming under sized. Provide a complete diagram of the natural gas distribution system showing all the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.