Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM07463
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07463
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The drain for the wall box serving an automatic clothes washer consists of a standpipe and a trap. The minimum size for the standpipe, its trap, and its fixture drain is 2". [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch or horizontal drain that is at least 3 inches in diameter. (The fixture drain cannot connect to the tailpiece of the mop sink.) Reference: Section 406.2, IPC 2018.]
2. Non-residential occupancies are required to provide hot water for, "culinary purposes, cleansing, laundry or building maintenance purposes." The mop sink and the automatic clothes washer shall be provided with hot water. Reference: Section 607.1, IPC 2018.
11/29/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change A dryer exhaust duct is not the same as an exhaust fan near the dryer. See Section 504. IMC 2018 for dryer exhaust duct requirements. [Initial comment: Provide an exhaust duct for the proposed clothes dryer. Reference: Section 504.8.6, IMC 2018.]