Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM07463
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07463
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2021 JPEELDA1 FIRE REVIEW Approved
09/27/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide an exhaust duct for the proposed clothes dryer. Reference: Section 504.8.6, IMC 2018.
09/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify how the drain plumbing for the new clothes washer relates to the existing building drain system on the plumbing plan. Reference: Section 107.2.1, IBC 2018.
2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch or horizontal drain that is at least 3 inches in diameter. (The fixture drain cannot connect to the tailpiece of the mop sink.) Reference: Section 406.2, IPC 2018.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 604.9, IPC 2018.
09/28/2021 ROBERT SHERRY WATER REVIEW Completed
10/06/2021 STEVE SHIELDS ZONING REVIEW Approved
10/06/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/06/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/14/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved