Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07460
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/08/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 10/13/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical review comments and provide a written response. Ref; Plan Sheet PV 2.5. The 3 line diagram for buildings ‘B’ and ‘C’ are identified as Building ‘A’ below the diagram. Please clarify. Ref; Plan Sheet PV 2.1, PV 2.3. Show panel ‘P4’ distance from the switchgear in the 3 line diagram for building ‘A’ along with the feeder conductor sizes and types.. Due to the distance of panel ‘P4’ from the existing service, and the location of the PV output interconnection, the tap rules of NEC art 240 may not apply. In that case, the feeder sizes for panel ‘P4’ may need to be increased as required per NEC art 705.12B(2). This requirement is because now there is a increase in the amount of current available or imposed on the feeder for panel ‘P4’. 400 amps + PV Output amps .. See NEC 240.4. Verify and show evidence per the manufacture of panel ‘P4’ that installing a 400 amp main circuit breaker on a panel that was installed as a main lug only panel configuration will not compromise the listing or performance of the panel. NEC 110.3B. Provide compliance with NEC 690.12, 690.56C for labeling and Rapid Shutdown Switch(s) where applicable for 3 PV systems. Include the Power Shutdown Initiation devices local to the PV arrays in the 3 line diagrams. In compliance NEC 690.12. Provide details for the grounding methods of the racking and Modules for the roof and Canopies. Provide a permanent directory at each PV Disconnecting Means as required per NEC 690.4(D), 705.10. Ref; 2018 IBC 107.2.1, 2017 NEC. |
| 11/02/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/02/2021 | VVERA1 | OUT TO CUSTOMER | Completed |