Permit Number: T21CM07427
Parcel: 140418560

Address:
3350 E MEDINA RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM07427
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07427

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Detail 2/S3.0. Provide load calculations for the existing open web steel joist and verify if it has the capacity to support 670# RTU as proposed. Check for Moment and End Reactions towards the near support.
2. Refer Detail 5/S3.0. Provide diagonal angle from HVAC support point to the bottom chord panel point. The open web steel joist’s top chord is not capable of supporting point loads at any point other than the panel point.

BUILDING REVIEW COMMENTS:
Denied
1. The incorrect edition of the NEC is listed. Provide an updated applicable codes list.
2. Provide existing/demolition plans as needed.
3. The egress from the office cannot pass through the F-2 use as this is of a higher hazard per Section 1016.2 #2. Provide a proper exit access or a protected access to exist discharge.
4. Ensure the fire partitions that separate the office area from the factory use maintain continuity in compliance with Section 708.4.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1.Provide supply and waster riser diagrams.
09/24/2021 JVINCEN1 FIRE REVIEW Reqs Change See building review comments. Provide written response to comments.
10/04/2021 SSHIELD1 DESIGN PROFESSIONAL REVIEW Passed
10/04/2021 STEVE SHIELDS ZONING REVIEW Approved
10/04/2021 STEVE SHIELDS ZONING_HISTORIC REVIEW Passed
10/04/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/04/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/13/2021 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2021 VVERA1 OUT TO CUSTOMER Completed