Permit Number: T21CM07418
Parcel: 125100240

Address:
1001 N RICHEY BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM07418
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Keynote 14 on sheet H1.0 calls for a 6" drain. [Second comment: Sheet H1.1 shows a 6" gravity drain from the splash pad, "…to waste" but, sheet H1.0 calls for a 4" drain connecting to the building sewer. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference: Section 706.2, IPC 2018.] [Initial comment: Show how the drainage from the splash pad will be conveyed to the public sewer system. Reference: Section 107.2.1, IBC 2018.]
04/11/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved