Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM07414
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/17/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
11/24/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PLEASE ADDRESS THE ELECTRICAL PLAN REVIEW COMMENTS AND PROVIDE A WRITTEN RESPONSE. 1. Per the response from PICKARD ARCHITECTS dated 11-10-2021. It was stated, ‘Note has been added at 1/A-2.0 that says no electrical works needed. Therefore no electrical plans will be needed”. This note could not be located in the resubmitted plans. Also be advised that any plans submitted must be sealed by a registrant registered in the State of Arizona. California seals are not valid in Arizona. 2. The application submitted for this project states in the ‘Description of Work’ “Remodel Kitchen. Remove dividing non load bearing wall units 6-10 (BLDG 2). The Site plan submitted shows BLDG #5 as “AREA OF WORK”. Not building #2. Please clarify. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |