Review Details: RESUBMITTAL

Permit Number - T21CM07412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2021 JPEELDA1 FIRE REVIEW Approved
11/08/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM07412

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approval Pending
1. All corrections complied
2. Approved/subject to field approval

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1). OK
2). Same, when drinking fountains are required they must comply with height requirements for people in wheelchairs & must comply with height requirements for standing people. -IPC 410.3 if one drinking is to be installed it must comply with exception of that code section. If another existing drinking fountain is mounted a standard height make that notation or illustration on the plumbing plans. P601 currently shows a single ADA height fountain
3). OK
4). OK
5). OK
6). OK