Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM07412
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 11/08/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM07412 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approval Pending 1. All corrections complied 2. Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied 1). OK 2). Same, when drinking fountains are required they must comply with height requirements for people in wheelchairs & must comply with height requirements for standing people. -IPC 410.3 if one drinking is to be installed it must comply with exception of that code section. If another existing drinking fountain is mounted a standard height make that notation or illustration on the plumbing plans. P601 currently shows a single ADA height fountain 3). OK 4). OK 5). OK 6). OK |