Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM07412
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2021 | JVINCEN1 | FIRE | REVIEW | Reqs Change | Remove "Roseville Fire Department" from cover sheet G001. Located in note, under deferred submittals. |
| 09/24/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM07412 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: DENIED 1. Section 5/S141 and 6/S141 on Structural Drawing S141 calls for 6x6 Douglas Fir No 2 Untreated Lumber. Verify how untreated wood will handle wet weather, make revision as necessary and resubmit. BUILDING REVIEW COMMENTS: APPROVED MECHANICAL REVIEW COMMENTS: DENIED 1. provide horn and strobe for walk-in cooler for notification of a refrigerant leak as is in freezer (IMC2018,1104.2.2) 2. duct smoke detectors on 2 new rooftop units shall be installed on the return air system (IMC2018,606.2.1) 3. Duct smoke detectors shall connected to the building fire alarm system (IMC2018,606.4.1) 4. Provide gas piping plan, with the gas pressure at the point of delivery, and the design pressure drop, maximum gas demand and specific gravity of the fuel gas and the total pipe length from the meter to the farthest appliance. (IFGC2018,402.3) ELECTRICAL REVIEW COMMENTS DENIED E131 ENTRY LIGHTING PLAN: Need to provide Note #38 E311 GUEST SERVICE & STARBUCKS POWER & SYSTEMS PLAN: Panel LP-10, circuit 17, 19 needs larger conductor to serve Dishwasher 6656 VA load. Note FS3 may need revised. E321 OFFICE & GROCERY PICKUP POWER & SYSTEMS PLANS: There is no note description for Note 287 and it is used on the sheet. E601 EQUIPMENT AND LIGHT FIXTURE SCHEDULE: Conductor too small for ACU-D for electrical split system schedule. E621 PANELBOARD SCHEDULES: LP-3 CB 24,26,28 for ACU-D might be undersized. E961 INTRUSION AREA PLANS: Cannot locate Notes 3 or 13. PLUMBING REVIEW COMMENTS: DENIED 1). Gray water pump detail #10 on P501 needs to illustrate the pumped connection to the sanitary drain system, showing it complies with IPC 712.35 also update P111 connection location 2). Drinking fountains need to be high/low type. IPC 410.3 Update P601 & Fixture Specification 2.2 C & D 3). The three compartment sink shall have an indirect waste connection, IPC 802.1.1 & 802.1.7 Update P311 & P601 4). All the fixtures, floor drains , floor sinks, service sink, appliances/dishwasher in the Starbucks area need to discharge to the grease system. except for the ice machine and or storage ice bins. update P311 Per Tucson Local Amendment IPC 1003.3 this local Amendment also limits the amount of Items to discharge to a Hydromechanical Grease Interceptor to a maximum of 4. 5). P501 Detail # 12 needs a shut off valve. IPC 606.2 6). P501 Detail #7 Tankless water heater needs it's own cold shut off that controls water only. IPC 503.1 |
| 10/04/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/04/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/04/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/13/2021 | ROBERT SHERRY | WATER | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2021 | VVERA1 | OUT TO CUSTOMER | Completed |