Permit Number: T21CM07406
Parcel: 134010120

Address:
205 S BROWN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM07406
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2021 STEVE SHIELDS ZONING REVIEW Approved
10/11/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
10/11/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/28/2021 JPEELDA1 FIRE REVIEW Approv-Cond Building under roof is 5,713 and exceeds 3,600. House is in an area without fire hydrants. You shall create a 2-hour fire wall betweem the new garage and the rest of the new construction on the existing house and or install fire sprinklers.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
10/28/2021 JPEELDA1 FIRE REVIEW Approv-Cond Building requires a 2 hour seperation so that they do not need to install fire sprinklers. TFD has advised them to create a 2 hour seperation between the new garage and the house. New plans shall be submitted prior but building shall confirm that the seperation is there and that they have a copy of the new plans for review onsite along with the approved plans.