Permit Number: T21CM07386
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM07386
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets A3 and A4 (Egress/Floor Plans); Sheet A7 (Section 2): The plans indicate a 48" pony wall between the Service Area and the Cook Area, while the Section 2/A7 is cut through that wall and indicates a partition wall to the ceiling. Please clarify.
2. Sheet A4; Floor Plan: The IBC Section 1109.11 requires a minimum number of accessible seats and standing spaces for tables and counters. Please provide a calculation on this sheet for the required number of spaces, and indicate those spaces on the floor plan.
3. Sheet A4; Floor Plan: For the bar counter required accessible spaces, please indicate on the plan the approach requirements per the ICC/ANSI Section 904.3.
4. Sheet A4; Floor Plan: Section 3/A7 is cut on the plan at the wall between the Cook Area and the Prep Area. That is not the correct location for that section cut. Please verify.
5. Sheet A6; RCP/Ceiling Plan: Please provide details on these drawings for the new hood support beam at the new interior wall and at the existing exterior wall.
6. Sheet A7 (Section 3); Sheet A4 (Floor Plan): Section 3 indicates an existing metal stud wall (opposite the new 3-2x10 beam) to support half of the hood weight (structural calculations also indicate that condition). That partition has a section cut 3/A8. Section 3/A8 indicates a pony wall. Please clarify and revise.
7. Sheet A8; Section 3: Please indicate the size of the wood studs in Section 3.
8. General: It is not clear if this building has an automatic sprinkler system. Please indicate on the drawings.
9. General: Please provide written responses to all review comments.
09/23/2021 JVINCEN1 FIRE REVIEW Approved
09/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/27/2021 ROBERT SHERRY WATER REVIEW Completed
10/04/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM07386
8898 E Tanque Verde Rd – C-1
TI Food Service (1st Review)

TRANSMITTAL: October 4, 2021

This site is located in the C-1 zone (UDC 4.7.20). Food Service with Alcoholic Beverage Service as an accessory use is a permitted use in this zone (Table 4.8-4), subject to Use Specific Standards 4.9.4.V.1, 3, & 5-9, 4.9.4.C.3, and 4.9.13.O.

1. Provide a copy of a approved site/development package that shows the patio in the configuration as shown on this plan.

2. Clearly demonstrate how the requirements of Use Specific Standards 4.9.4.V.1, 3, & 5-9, 4.9.4.C.3, and 4.9.13.O are met on the plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/04/2021 SSHIELD1 ENGINEERING REVIEW Passed
10/04/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/11/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved