Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM07375
Parcel: 126162880

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07375
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM07375
Roof top Solar Panels (1st Review)
4012 E CALLE CHICA

TRANSMITTAL DATE: October 4, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating.



COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2021 VVERA1 OUT TO CUSTOMER Completed