Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM07354
Parcel: 140324650

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM07354
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM07354
Roof top Solar Panels (1st Review)
4376 E OCOTILLO DESERT

TRANSMITTAL DATE: September 9, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Provide an appropriate Maximum Photovoltaic System Voltage (Vpp x 1.14) NEC 690.7 and Table 690.7 (16 degrees F lowest ambient). Show a collector module design with a corrected voltage maximum not exceeding 600 volts.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2021 VVERA1 OUT TO CUSTOMER Completed